SPD installation is a hazardous activity. The following safety rules must be strictly observed:
-
De-energize the Circuit: ALWAYS disconnect and lock out all power sources to the panel before installation or servicing. Never work on live equipment.
-
Qualified Personnel Only: Installation must be performed by a qualified electrician or trained personnel in compliance with all national and local electrical codes.
-
Reliable Grounding: Ensure that the system’s Neutral (N) and Ground (G) are properly and reliably connected according to code. Improper or missing grounding will impair operation and may lead to SPD failure.
-
NEVER Hi-Pot Test: Never perform a dielectric strength (Hi-Pot) test on a circuit with the SPD connected. The high test voltage will permanently damage or prematurely fail the SPD’s MOV components.
-
Lead Length: Keep all connecting wires, especially the neutral wire, as short and straight as possible to minimize inductive impedance and maximize protection performance. Prosurge products provide ample lead length (e.g., 30 inches); cut off excess length rather than coiling it.
-
VPR (Voltage Protection Rating): This is a key performance indicator defined by the UL 1449 standard. A lower VPR value signifies better clamping performance, meaning the SPD can limit the surge voltage to a lower level, providing superior protection for downstream sensitive electronic equipment. For example, for a 120/240V system, a lower L-N VPR (e.g., 600V) is preferable to a higher one (e.g., 1200V).
-
MCOV (Maximum Continuous Operating Voltage): This is the maximum RMS voltage the SPD can safely endure continuously. The MCOV rating of the chosen SPD must be higher than the nominal voltage of the electrical system it is protecting. For example, for a 120/240V system, the L-N MCOV should be 150V or higher. Using an SPD with an MCOV that is too low (e.g., installing a 120V-rated SPD on a 240V system) will cause the device to fail instantly due to continuous overvoltage.
PTMOV (Protected Thermally MOV) is Prosurge’s patented technology—a Metal Oxide Varistor with an integrated thermal protection mechanism and arc extinguish device. Its core advantages are:
-
Superior Safety: Traditional MOVs can overheat and catch fire when subjected to continuous overvoltage or surges exceeding their rating. The PTMOV incorporates an internal thermal disconnector that swiftly and safely disconnects the MOV element from the circuit upon detecting abnormal temperature rise. Its advanced arc extinguishing technology effectively eliminates the risk of fire.
-
High Fault Current Withstand Capability: Due to its excellent arc suppression, Prosurge SPDs based on PTMOV technology achieve a high Short-Circuit Current Rating (SCCR) of up to 200kArms. This means that even in the unlikely event of a failure, the SPD can withstand a fault current of up to 200,000 amperes without violent rupture or explosion, ensuring the safety of personnel and equipment. Most models achieve this SCCR without requiring an external fuse or circuit breaker, simplifying design and reducing system cost.
“Full Mode Protection” means the SPD provides surge suppression between all possible combinations of conductors in the power system, including:
-
L-N (Line-to-Neutral)
-
L-G (Line-to-Ground)
-
N-G (Neutral-to-Ground)
-
L-L (Line-to-Line, for split-phase or three-phase systems)
Implementing full mode protection is a best practice because transient overvoltages can occur between any conductor combination. Most Prosurge panel SPD series (e.g., PSP C, HPSP, PS) offer a full mode protection option to ensure comprehensive protection. To accommodate different power distribution systems (e.g., delta systems without a neutral), Prosurge also provides customizable protection modes (e.g., L-G, L-L only).
According to the ANSI/UL 1449 5th Edition, the installation location differentiates Type 1 and Type 2 SPDs:
-
Type 1 SPD: Designed for installation between the secondary of the service transformer and the line side of the service equipment overcurrent device. This includes the meter socket or the main breaker’s line side. They are intended to be installed without an external overcurrent protective device and have a very high capacity, capable of handling a portion of a direct lightning strike.
-
Type 2 SPD: Designed for installation on the load side of the service equipment overcurrent device. This is the most common location, at the output of the main breaker in the main distribution panel or in sub-panels, protecting downstream branch circuits.
Selection Advice:
-
Choose Type 1 if your application requires the highest level of safety and withstand capability, such as when replacing an old SPD in the meter socket or when concerned about direct lightning strikes on the service entrance.
-
For the vast majority of new installations or retrofits, installing the SPD after the main breaker (Type 2) is the standard and most common practice.
-
Many Prosurge series (e.g., PSP C, HPSP, PS, 20PSP, PSP B) are dual-certified as both Type 1 and Type 2, offering maximum installation flexibility.
Selecting the correct SPD depends on your application environment, system voltage, and the required level of protection. Use the following guide for an initial selection:
| Application Scenario | Recommended Series | Key Features & Rationale |
|---|---|---|
| Residential (Homes) | POSP 20 | Plug-on design for easy installation; 20kA nominal discharge current is sufficient to handle lightning strikes and utility switching transients in residential areas. |
| Commercial Buildings (Offices, Retail) | PSP B, 20PSP | Compact design saves panel space; UL Type 1 & 2 listed for installation in main or sub-distribution panels. |
| Industrial Facilities (Factories, Workshops) | PSP C, HPSP, PS | High surge capacity to handle the more severe surge environments found in industrial settings; optional metal enclosures for harsh physical conditions; HPSP and PS offer extreme energy handling. |
| Telecom & Data Centers | PSP C, HPSP, PS | Low Voltage Protection Ratings (VPR) to safeguard sensitive IT and communication equipment; optional Sine Wave Tracking to suppress high-frequency noise; high reliability for business-critical operations. |
| Renewable Energy (Solar, Wind) | PSP C, HPSP, PS | Suitable for high-exposure locations; can withstand large surge energies from direct or indirect lightning strikes, protecting expensive inverters and control systems. |
| Hospitals & Critical Infrastructure | PS Series | Features AFM technology for “anticipated failure monitoring,” providing early warning before complete failure, enabling planned maintenance and maximizing power continuity. |
| LED Lighting, Security Systems | PSP E, PSPF | Extremely compact, making them easy to install at the equipment level or in small sub-panels, providing precise point-of-use protection for specific sensitive devices. |
A1: Prosurge offers a comprehensive SPD product line to address needs ranging from residential to mission-critical infrastructure. The main series and their positioning are as follows:
POSP 20 Series: Plug-on UL1449 Type 1 SPDs designed for residential and light commercial applications. They can be directly plugged into mainstream load centers (breaker panels), providing convenient primary protection for an entire home or small facility.
PSP B / 20PSP Series: Compact Panel SPDs suitable for low to moderate exposure environments. Their compact size and waterproof plastic enclosures make them ideal for commercial, industrial, and telecommunications applications. The 20PSP features a nominal discharge current (In) of 20kA, while the PSP B has an In of 10kA.
PSP C / HPSP Series: High-Performance Panel SPDs designed for critical commercial and industrial environments. They offer higher surge current capacity (PSP C up to 300kA per phase, HPSP up to 600kA per phase) and optional features like EMI/RFI filtering and metal enclosures for superior protection.
PS Series: Ultra-High Capacity Panel SPDs intended for mission-critical applications. Featuring a modular design (SMTMOV/HSMTMOV), this series boasts the highest surge capacity (up to 900kA per phase) and unique Anticipatory Failure Monitoring (AFM) technology with a three-stage status indication (Blue – Yellow – Red) to ensure continuous, reliable protection.
PSP E / PSPF Series: Extra-Compact SPDs. The PSP E is specifically designed for single-phase systems, while the PSPF offers various protection mode combinations. Both are ideal for protecting sensitive equipment like commercial LED lighting, telecom devices, HVAC systems, and medical electronics where space and cost are key considerations.
Based on UL 1449:2021 Ed.5 (Surge Protective Devices)
A: The 5th Edition defines six categories, based on installation location and component completeness:
-
Type 1 (Listed, field-installable): Permanently connected SPDs for installation between the service transformer and the line side of the main service overcurrent device, or anywhere downstream. Includes watt-hour meter socket types and Molded Case SPDs that do not require external overcurrent protection.
-
Type 2 (Listed, field-installable): Permanently connected SPDs for installation on the load side of the main service overcurrent device, including branch panels and Molded Case SPDs. May require external overcurrent protection per listing.
-
Type 3 (Listed, field-installable): Point-of-utilization SPDs. Typically cord-connected, direct plug-in, or receptacle types. Must be installed at least 10 meters (30 feet) from the service panel (conductor length exclusive of SPD leads).
-
Type 1, 2, 3 Component Assemblies (Recognized Component, NOT field-installable): These are Type 4 component assemblies with integral or external short circuit protection. They have passed safety failure tests but have conditions of acceptability (e.g., exposed terminals) requiring factory installation inside listed equipment.
-
Type 4 Component Assemblies (Recognized Component, NOT field-installable): An assembly of one or more Type 5 components with a disconnector (integral or external) or means to comply with limited current tests. Incomplete as an SPD; requires further evaluation.
-
Type 5 (Recognized Component, NOT field-installable): Discrete components (e.g., MOVs, GDTs) that may be mounted on a PCB or provided in an enclosure. The building blocks of SPDs; incomplete and require full evaluation.
Though we try our best to offer an extensive, thorough product presentation on our website, catalogs and other documents, we believe the best way for model selecting is to consult with us with your requirement and then our professional will recommend a suitable model.
The following examines a few of the key differences between Underwriters Laboratory’s required test for surge protective devices (SPDs); ANSI/UL 1449 Third Edition and the International Electrotechnical Commission (IEC) required test for SPDs, IEC 61643-1.
Short Circuit Current Rating (SCCR): The capacity of current with which the tested SPD can withstand at the terminals where connected, without breaching the enclosure in any way.
UL: Tests the full product at twice the nominal voltage to see if entire product is completely offline. The entire product (as shipped) is tested; including metal oxide varistors (MOVs).
IEC: Test only looks at the terminals and the physical connections to determine if they are robust enough to handle the fault. MOVs are replaced with a copper block and a manufacturer’s recommended fuse is placed in-line (external to the device).
Imax: Per IEC 61643-1 – The crest value of a current through the SPD having an 8/20 waveshape and magnitude according to the test sequence of the class II operating duty test.
UL: Does not recognize the need for an Imax test.
IEC: An operating duty cycle test is used to ramp up to an Imax point (determined by the manufacturer). This is meant to find “blind points” within the design when subjected to a high level impulse. This is conducted as a life expectancy or robustness test. The fuse needs to withstand Imax, and the test checks thermal stability of the SPD (after each duty cycle impulse bringing the SPD up to its maximum continuous operating voltage MCOV) and its physical condition。
I nominal: The crest value of the current through the SPD having a current waveshape of 8/20.
UL: I nominal test is similar to the IEC’s, however, the I nominal results do not link to a Up value (a value used internationally for electrical coordination). Instead, UL uses I nominal to determine a product’s Voltage Protection Rating (VPR). Levels are limited to a maximum of 20 kA. The SPD remains functional after 15 surges.
IEC: Does not limit I nominal testing to 20kA, however, the manufacturer’s selected In level is used to get a Up value, a value considered to be the protective performance of the SPD. This value is used for electrical coordination(ratings of building wire, equipment).
Therefore the goal of the manufacturer is to try to attain the highest Inominal level with the lowest Up results. Many manufactures opt to only test as high as 20 kA so they will appear to have a low Up.
Class versus category
UL: UL Type designation is a location designator with a difference to the way I nominal is tested (for device which provides SCCR needs to be included and survive when doing I nominal testing).
IEC: Designates certain tests as a class I, II, or III. Class designation between I and II has to do with the impulse applied – Class I; an I imp test (10×350) and a class II – 8 x 20 μs.
The IEC designates certain tests as a class I, II, or III and can beconfused with UL’s Type I, II, III, or IV designations. There is some validity to both identifying the product’s approved installation location (UL) and applying a more robust impulse/waveform to those products that will be installed in harsher locations (IEC).
Waveforms: A graph of an impulse wave that shows its shape and changes in amplitude with time.
UL: Recognizes the 8 x 20 μs waveform.
IEC: The IEC incorporates 2 waveforms into their test, the 8 x 20 μs which is used for class II testing to represent surges induced onto power lines. And the 10 x 350 μs waveform which is used for class I testing that represents partial or direct lightning currents (due to building or power line strikes).The IEC also uses other ring wave type waveforms for point of use (class III) tests.
Choosing the right surge arrester(s) is a key factor to guarantee correct protection of the installation. A poorly designed Lightning & Surge protection system may lead to early ageing of the SPD and potential failure of the protective devices in the installation allowing damage to the primary systems up stream, thus defeating the rationale behind the protection being installed
Prosurge does not provide a set of rules and guides to support acorrect design of the protection system according to the application. However we follow the IEC and UL lightning and surge protection standards. With this in mind we provide a cascaded system as laid down in the rules of the standard, not the rules of Prosurge.
In the field of industrial applications, a standard practice is to install a cascaded protection system based on several coordinated protective devices installed at different stages (LPZ’s). The benefit of this strategy is the fact that it allows a high discharge capacity close to the installation entrance along with a low residual voltage (level of protection) at the main incomer of installation of sensitive equipment.
The design of such a protective system is, amongst other factors, based on the assessment of information such as existence of a lightning rod (Lightning Protection System) and type of incoming power supply lines, secondary primary equipment and data systems.
The solutions provide protection against either Transient or Permanent (TOV) overvoltages or against both of them (T+P) simultaneously.
The final product choice depends on parameters such as: type of installation, type of network disconnection (operation on MCB or RCD), auto reclosing, breaking capacity, etc.
Usually you can refer IEC61643- Low-voltage surge protective devices – Part 12:Surge protective devices connected to low-voltage power distribution systems -Selection and application principles
Photovoltaic systems are technologically highly sensitive and a direct lightning strike would definitely destroy it. There is also yet another hazard,as a lightning strike could create surge voltage near the solar power system and these surge voltages can also destroy the system. The inverter is the primary point in need of protection. Usually, inverters will integrate surge-voltage protectors into their inverters. However, since these components only discharge small voltage peaks, you should consider using surge protective devices (SPD) in individual cases.
In the past, some manufacturers have used joule ratings in their specifications. They are not considered a good indicator for SPD performance and not recognized by any standard organizations. Prosurge doesn’t support this specification also.
Response time specifications are not supported by any standards organizations overseeing Surge Protective Devices.IEEE C62.62 Standard Test Specification for SPDs specifically mentions it should not be used as a specification.
The US power distribution system is a TN-C-S system. This implies that the Neutral and Ground conductors are bonded at the service entrance of each, and every, facility or separately derived sub-system. This means that the neutral-to-ground (N-G) protection mode within a multi-mode SPD installed at the service entrance panel is basically redundant. Further from this N-G bondpoint, such as in branch distribution panels, the need for this additional mode of protection is more warranted. In addition to the N-G protection mode, some SPDs can include line-to-neutral (L-N) and line-to-line (L-L) protection. On a three phase WYE system, the need for L-L protection is questionable as balanced L-N protection also provides a measure of protection on the L-L conductors.
Changes to the 2002 edition of the National Electrical Code® (NEC®) (www.nfpa.org) have precluded the use of SPDs on ungrounded delta power distribution systems. Behind this rather broad statement is the intention that SPDs should not be connected L-G as by so doing these modes of protection are creating pseudo grounds to the floating system. Modes of protection connected L-L are however acceptable.The high-leg delta system is a grounded system and as such allows for protection modes to be connected L-L and L-N or L-G.
The installation of SPDs is often poorly understood. A good SPD, incorrectly installed, can prove of little benefit in real-life surge conditions. The very high rate-of-change of current, typical of a surge transient, will develop significant volt drops on the leads connecting the SPD to the panel or equipment being protected. This can mean higher than desired voltages reaching the equipment during such a surge condition. Prosurge suggests that measures to counteract this effect include locating the SPD so as to keep interconnecting lead lengths as short as possible, twisting these leads together. Using a heavier gauge AWG cable helps to some extent but this is only a second order effect. It is also important to keep protected and unprotected circuits and leads separate to avoid cross coupling of transient energy.
This is a difficult question and depends on many aspects including – site exposure, regional is okeraunic levels and utility supply. A statistical study of lightning strike probability reveals that the average lightning discharge is between 30 and 40kA, while only 10% of lightning discharges exceed 100kA. Given that a strike to a transmission feeder is likely to share the total current received into anumber of distribution paths, the reality of the surge current entering a facility can be very much less than that of the lightning strike which precipitate it.
The ANSI/IEEE C62.41.1-2002 standard seeks to characterize the electrical environment at different locations throughout a facility. It defines the service entrance location as between a B and C environment, meaning that surge currents up to 10kA 8/20 can be experienced in such locations. This said,SPDs located in such environments are often rated above such levels to provide a suitable operating life expectancy, 100kA/phase being typical.
What are surges transients, and temporary over-voltages, and what are their typical characteristics?
Although often used as separate terms in the surge industry, Transients and Surges are the same phenomenon. Transients and Surges can be current, voltage, or both and can have peak values in excess of 10kA or 10kV. They are typically of very short duration (usually >10 µs & <1 ms), with a waveform that has a very rapid rise to the peak and then falls off at a much slower rate. Transients and Surges can be caused by external sources such as lightning or a short circuit, or from internal sources such as Contactor switching, Variable Speed Drives, Capacitor switching, etc.
Temporary over voltages (TOVs) are oscillatory phase-to-ground or phase-to-phase over voltages that can last as little as a few seconds or as long as several minutes. Sources of TOV’s include fault reclosing, load switching, ground impedance shifts,single-phase faults and ferroresonance effects to name a few. Due to their potentially high voltage and long duration, TOV’s can be very detrimental to MOV-based SPD’s. An extended TOV can cause permanent damage to an SPD and render the unit inoperable. Note that while UL 1449 (3rd Edition) ensures that the SPD will not create a safety hazard under these conditions, SPDs are not designed to protect against TOVs.
A direct lighting strike is the most powerful and difficult surge to protect against. Prosurge recommend that Proper grounding and bonding of the electrical system and employing proper surge protection can protect sensitive equipment. A SPD with a higher single surge current rating will perform best against this type of event, if the unit is properly installed and the grounding system is adequate.The maximum single withstand surge current rating is defined in IEEE SPD Standard C62.62.
SVR was part of an earlier version of UL 1449 Edition and is no longer used in the UL 1449 standard. The SVR was replaced by VPR.
VPR is part of the UL 1449 3rd Edition and is the clamping performance data for SPDs. Each SPD mode is subjected to a 6kV/3kA combination surge wave and its measured clamping value is rounded up to the nearest value based on table 63.1 from UL 1449 3rd Edition.
UL 96A is the standard for Lightning Protection systems. For a building to meet UL 96A is must have a Type 1 SPD with a Nominal Discharge Current rating of 20kA installed at the service entrance.
Some key differences between Type 1 and Type 2 SPDs are:
- External Overcurrent Protection. Type 2 SPDs may require external overcurrent
protection or it may be included within the SPD. Type 1 SPDs generally include
overcurrent protection within the SPD or other means to satisfy the requirements
of the standard; thus, Type 1 SPDs and Type 2 SPDs that do not require external
overcurrent protection devices eliminate the potential for installing an incorrectly
rated (mismatched) overcurrent protection device with the SPD. - Nominal Discharge Current Ratings. Available Nominal Discharge Current (In)
ratings of Type 1 SPDs are 10 kA or 20 kA; whereas, Type 2 SPDs may have 3
kA , 5 kA, 10 kA or 20 kA Nominal Discharge Current ratings. - UL 1283 EMI/RFI Filtering. Some UL 1449 Listed SPDs include filter circuits
that have been evaluated as a UL 1283 (Standard for Electromagnetic Interference
Filters) filter. These are complimentary UL Listed as a UL 1283 filter and a UL
1449 SPD. By definition and the scope of UL 1283, UL 1283 Listed filters are
evaluated for load-side applications only, not line-side applications.
Consequently, UL will not complimentary list a Type 1 SPD as a UL 1283 Listed
filter. However, a Type 1 SPD might include a UL 1283 filter as a Recognized
Component within a Listed Type 1 SPD, which has been fully evaluated for lineside
usage. Manufacturers of such products generally offer the identical SPD as a
Type 2 UL 1449 Listed SPD with complimentary Listing as a UL 1283 Listed
filter. - Capacitors. Capacitors utilized in Type 1 SPDs may be evaluated for safety
differently than in Type 2 SPDs. All capacitors in Type 1 SPD applications are
evaluated to UL 810 (Standard for Capacitors). This includes filtering capacitors
referenced above in UL 1283 (Standard for Electromagnetic Interference Filters)
applications. Capacitors in Type 2 SPDs are evaluated to UL 1414 (Standard for
Capacitors and Suppressors for Radio- and Television-Type Appliances) and/or
UL 1283 (Standard for Electromagnetic Interference Filters).
Type 1 SPDs (Listed) – Permanently connected, hard-wired SPDs intended for
installation between the secondary of the service transformer and the line side of the main
service equipment overcurrent protective device, as well as the load side of the main
service equipment (i.e. Type 1’s can be installed anywhere within the distribution
system). Type 1 SPDs include watt-hour meter socket enclosure type SPDs. Being on the
line side of the service disconnect where there are no overcurrent protective devices to
protect an SPD, Type 1 SPDs must be listed without the use of an external overcurrent
protective device. The Nominal Discharge Current Rating for Type 1 SPDs is either
10kA or 20kA.
Type 2 SPDs (Listed) – Permanently connected, hard-wired SPDs intended for
installation on the load side of the main service equipment overcurrent protective device.
These SPDs may also be installed at the main service equipment, but must be installed on
the load side of the main service overcurrent protective device. Type 2 SPDs may or may
not require an overcurrent protection device per their NRTL listing. If a specific
overcurrent protection is required, the SPD’s NRTL listing file and labeling/instructions
are required to note the size and type of overcurrent protective device. Note: In some
cases the overcurrent protective device used can impact the nominal discharge rating of
the SPD. For example, the SPD may have a 10 kA nominal discharge current rating
when protected by a 30 Amp circuit breaker and a 20 kA nominal discharge current
rating when protected by a different but specific make and model of overcurrent
protection device. The Nominal Discharge Current Rating for Type 2 SPDs is 3 kA, 5
kA, 10 kA, or 20 kA.
Type 3 SPDs (Listed) – These SPDs are called, ‘Point of Utilization SPDs’, which are to
be installed at a minimum conductor length of 10 meter (30 feet) from the electrical
service panel unless they are evaluated at Type 2 SPDs (that is, they receive a Nominal
Discharge Current Rating of 3 kA minimum). Typically, these are cord-connected surge
strips, direct plug-in SPDs, or receptacle-type SPDs installed at the utilization equipment
being protected (i.e. computers, copy machines, etc.).
Type 1, 2, 3 Component Assembly SPDs (Component Recognized) – These SPDs are
intended to be factory installed into electrical distribution equipment or end-use
equipment. These are Recognized Component SPDs evaluated for use in Type 1, 2 or 3
SPD applications. Such component SPDs must pass all the same electrical safety failure
tests as listed Type 1, 2 or 3 SPDs. While these SPDs are 100% compliant from a safety
failure testing point of view, these Type 1, 2 and 3 component assembly SPDs have
conditions of acceptability such as exposed terminals or other mechanical construction
that requires them to be installed or housed within a listed assembly to provide protection
from exposure to live parts or other requirements. These Type 1, 2 or 3 Recognized
Component SPDs should not be confused with ANSI/UL 1449-2006 Type 4 Component
Assemblies and Type 5 discrete SPD components that require additional components
(possibly safety disconnectors), design and testing in order to be used as a complete surge
protective device.
Type 4 Component Assembly SPD (Component Recognized) –– These component
assemblies consist of one or more Type 5 SPD components together with a disconnector
(integral or external) or a means of complying with the limited current tests in UL 1449,
Section 39.4. These are incomplete SPD assemblies, which typically are installed in
listed end-use products as long as all conditions of acceptability are met. These Type 4
component assemblies are incomplete as an SPD, require further evaluation and are not
permitted to be installed in the field as a stand-alone SPD. Often, these devices require
additional overcurrent protection.
Type 5 SPD (Component Recognized) – Discrete component surge protection devices,
such as MOVs that may be mounted on a printed wiring board, connected by its leads or
provided within an enclosure with mounting means and wiring terminations. These Type
5 SPD components are incomplete as an SPD, require further evaluation and are not
permitted to be installed in the field as a stand-alone SPD. Type 5 SPDs are generally the
components used in the design and construction of complete SPDs or other SPD
assemblies.
SSCR-Short Circuit Current Rating. The suitability of an SPD for use on an AC power circuit that is capable of delivering not more than a declared rms symmetrical current at a declared voltage during a short circuit condition. SCCR is not the same as AIC (Amp Interrupting Capacity). SCCR is the amount of “available”current that the SPD can be subjected to and safely disconnect from the power source under short circuit conditions. The amount of current “interrupted” by the SPD is typically significantly less than the “available” current.
UL 1449 and the National Electric Code (NEC) require the SCCR (Short Circuit Current Rating) to be marked on all SPD units. It is not a surge rating, but the maximum allowable current a SPD can interrupt in the event of failure. The NEC/UL has a requirement that the SPD be tested and labelled with a SCCR equal to, or greater than the available fault current at that point in the system.
When specifying SPD, submit a clear, concise specification detailing the required performance and design features. A minimum specification should include:
• UL surge rating
• Suppression rating
• Short circuit rating
• Peak surge current per mode (L-N, L-G, and N-G)
• voltage and configuration of electrical service
SPD is a device designed to limit surge energy to electrical equipment. It does this by diverting or limiting surge current. An SPD is wired in parallel to the equipment it is intended to protect. Once the surge voltage exceeds its designed rating it “begins to clamp” and starts to conduct energy directly to the electrical grounding system. An SPD has a very low resistance during this time and “shorts” the energy to ground. Once the surge is over it “opens” up, so it does not trigger upstream circuit breakers.