BPS12.5V series
power configuration: “1+1” or “2+0”, 2P
L-N (MOV module): 12.5kA 10/350μs per pole
N-PE (GDT module):25kA 10/350 ~50kA 10/350
Type 1 + Type 2 surge protective device
BPS12.5V series
power configuration: “”3+0”, 3P SPD
12.5kA 10/350μs per pole
Type 1 + Type 2 surge protective device
BPS12.5V series
power configuration: “3+1” or “4+0”, 4P
L-N (MOV module): 12.5kA 10/350μs per pole
N-PE (GDT module):50kA 10/350
Type 1 + Type 2 surge protector
The BPS12.5V is class I & class II (or T1+T2 ) prewired two poles SPD designed for low-voltage power system lightning current & surge protection, especially for location of high risk exposure or LPZ 0-2 building entrances ( IEC 62305-4) to against the damage from direct or close lightning strikes.
With built in PROSURGE high energy MOV, BPS12.5V 2P ensures remarkable lightning current discharge capacity up to 12.5kA 10/350μs. The unique design of thermal protection provides quick thermal response and secure disconnection. BPS12.5V 2P is ideal protection for environments with frequent switching operations or lightning strikes.
With built in PROSURGE high energy MOV and GDT, BP12.5V PN SPD ensures remarkable lightning current discharge capacity up to 12.5 kA 10/350μs(L-N) and 25kA to 50kA 10/350μs(N-PE).
BPS12.5V/…/PN SPD is prewired and easy for electrical installation of TN/TT single phase system as “1+1” protection circuit.
- TUV certified T1+ T2 SPD per IEC/EN 61643-11 standard
- Prewired two poles SPD (“1+1” circuit) for use in single phase
- 18mm narrow model design, pluggable module for easy replacement without the need to remove system wiring.
- Unique thermal disconnector design provides quick thermal response and secure disconnection
- Lightning current capacity up to 12.5kA10/350μs(L-N), 50kA 10/350μs( (N-PE)
- Surge current capability up to 80kA 8/20μs(L-N), 100kA 8/20μs(N-PE)
- Low voltage protection level
- High short-circuit current rating up to 50kArms, suitable for application in most AC power systems.
- Degradation failure indication and optional remote signal contact.
- Wide operating temperature -40ºC ~85ºC
- 35mm DIN-rail mounting
- Comply with UL1449 5th, IEEE C62.41,CSA C22.2 standards
The BPS12.5V 3P is class I & class II (or T1+T2 ) prewired three poles SPD designed for low-voltage power system lightning current & surge protection, especially for location of high risk exposure or LPZ 0-2 building entrances ( IEC 62305-4) to against the damage from direct or close lightning strikes.
With built in PROSURGE high energy MOV, BPS12.5V 3P ensures remarkable lightning current discharge capacity up to 12.5kA 10/350μs. The unique design of thermal protection provides quick thermal response and secure disconnection. BPS12.5V 3P is ideal protection for environments with frequent switching operations or lightning strikes.
- TUV certified T1+ T2 SPD per IEC/EN 61643-11 standard.
- Prewired three poles SPD (“3+0” circuit) for use in three phase IT / TN-C systems
- 18mm narrow model design, pluggable module for easy replacement without the need to remove system wiring.
- Unique thermal disconnector design provides quick thermal response and secure disconnection
- Lightning current capacity up to 12.5kA10/350μs
- Surge current capability up to 80kA 8/20μs
- Low voltage protection level
- High short-circuit current rating up to 50kArms, suitable for application in most AC power systems.
- Degradation failure indication and optional remote signal contact.
- Wide operating temperature -40ºC ~85ºC
- 35mm DIN-rail mounting
- Comply with UL1449 5th, IEEE C62.41,CSA C22.2 standards
The BPS12.5V 4P is class I & class II (or T1+T2 ) prewired four poles SPD designed for low-voltage power system lightning current & surge protection, especially for location of high risk exposure or LPZ 0-2 building entrances ( IEC 62305-4) to against the damage from direct or close lightning strikes.
With built in PROSURGE high energy MOV, BPS12.5V 4P SPD ensures remarkable lightning current discharge capacity up to 12.5kA 10/350μs. The unique design of thermal protection provides quick thermal response and secure disconnection. BPS12.5V 4P is ideal protection for environments with frequent switching operations or lightning strikes.
With built in PROSURGE high energy MOV and GDT, BP12.5V 3PN SPD ensures remarkable lightning current discharge capacity up to 12.5 kA 10/350μs(L-N) and 50kA 10/350μs(N-PE).
BPS12.5V/…/3PN50 SPD is prewired and easy for electrical installation of TN/TT three phase system as “3+1” protection circuit.
- TUV certified T1+ T2 SPD per IEC/EN 61643-11 standard
- Prewired two poles SPD (“1+1” circuit) for use in single phase
- 18mm narrow model design, pluggable module for easy replacement without the need to remove system wiring.
- Unique thermal disconnector design provides quick thermal response and secure disconnection
- Lightning current capacity up to 12,5kA10/350μs(L-N), 25kA 10/350μs( (N-PE)
- Surge current capability up to 80kA 8/20μs(L-N), 50kA 8/20μs(N-PE)
- Low voltage protection level
- High short-circuit current rating up to 50kArms, suitable for application in most AC power systems.
- Degradation failure indication and optional remote signal contact.
- Wide operating temperature -40ºC ~85ºC
- 35mm DIN-rail mounting
- Comply with UL1449 5th, IEEE C62.41,CSA C22.2 standards
Prosurge Surge Protection Device Products Family
Click to explore our extensive surge protection devices and other lightning protection products.
DIN-rail SPD for AC Power Supply
Panel SPD for AC Power Supply
IEC Standard
UL Standard
Other Surge and Lightning Protection Products
Email Prosurge and Get Reply in 2 Hours
see how competitive our price is : )
Live chat with us by clicking the chat button on the bottom right corner
Fill the Contact Form and Get Reply in 2 Hours
For North American market, please contact
For other markets, please contact
+86 757 8632 7660